Wednesday, 5 January 2022
Thursday, 16 December 2021
How to Find The Suitable Size of Cable & Wire for Electrical Wiring Installation? With Examples
How to Find The Suitable Size of Cable & Wire for Electrical Wiring Installation? With Examples
Remember that it's far very crucial to choose proper wire size while sizing a wire for electrical installations. An inappropriate size of wire for heavy loads current can also create chaos which results in failure of the electrical system, hazardous fire and serious injuries.
Voltage Drop in Cables
Whenever the current flows through the conductor, there will be a voltage drops in that conductor. Normally, voltage drop may be neglected for small length of conductors but in case of a lower diameter and long length conductors we should consider a significant voltage drops for proper wiring installation and future load management.
According to Institute of Electrical and Electronics Engineers (IEEE) rule B-23, at any point between a power supply terminal and installation, voltage drop should not increase above 2.5% of provided (supply) voltage
Example:
Let us assume , the supply voltage is 230V AC, then the value of permissible voltage drop should be;
- Permissible Voltage Drop = 230 x (2.5/100) = 5.75V
Similarly, if the supply voltage is 110V AC, the Permissible Voltage Drop should be not more than 2.75V ( 110V x 2.5%).
In electrical wiring circuits, for sub circuits the value of voltage drop should be half of that permissible voltage drop.
Normally, the voltage drop is expressed in Ampere per meter (A / m)
Tables & Charts for Proper Cable & Wire Sizes
Below are the important tables which you should follow for determining the proper size of cable for Electrical Wiring Installation
How to calculate Voltage Drop in a Cable?
Step no. 1: Calculate the maximum allowable voltage drop.
Step no. 2: Calculate the load current
Step no. 3: After finding the load current select a proper cable from table 1
Step no. 4: from table 1 find the voltage drop of the cable and multiply with the length of cable
Step no. 5: Now
multiply this calculated value of volt drop by load factor where;
Load factor = Load Current to be taken by Cable/ Rated
Current of Cable given in the table.
This is
the value of Volt drop in the cables when load current flows through it.
Step no. 6: If
the calculated value of voltage drop is less than the value calculated in step
(1) (Maximum allowable voltage drop), than the size of selected cable is proper
Step no. 7: If the calculated value of voltage drop is greater than the value calculated in step (1) (Maximum allowable voltage drop), than calculate voltage drop for the next (greater in size) cable and so on until the calculated value of voltage drop became less than the maximum allowable voltage drop calculated in step (1).
Example :
For Electrical wiring in a building, Total load is 5kW and
the length of the cable from Main panel to sub circuit is 40 feet. Supply
voltages is 230V and temperature is 40°C.
Find the suitable size of cable which is going through conduits .
Solution:-
Ø Total Load = 5kW
Ø Let us assume at max 20% overload occurs i.e.
1.2*5kW=6kW or 6000W
Now for 6000W load current will flow i.e. 6000/230= 26.08A
ØNow we have to select the size of cable from table 1 for 26.08A current which is 7/0.036 (28 Amperes). It means we can use 7/0.036 cable according to table 1.
Ø Now check the selected (7/0.036) cable with
temperature factor in Table 3, so the temperature factor is 0.94 (in table 3) at 40°C
and current carrying capacity of
(7/0.036) is 28A, therefore, current carrying capacity of this cable at 40°C
(104°F) would be
Current rating for 40°C = 28 x 0.94 = 26.32 Amp.
Maximum current carrying capacity is 26.32 A and actual is 26.08A.Hence this size of cable (7/0.036) is also suitable.
Ø
Now find the voltage drop for 100 feet for this
(7/0.036) cable is 7V, But in our case, the length of cable is 40 feet. Therefore,
the voltage drop for 40 feet cable would be;
Actual Voltage drop for 40 feet = (7 x 40/100) x (26.08/28)
= 2.608V
And Allowable voltage drop = (2.5 x 220)/100 = 5.5V
Here The Actual Voltage Drop (2.608V) is less than that of maximum allowable voltage drop of 5.5V. Therefore, the most suitable cable size is (7/0.036) for that given load.
Saturday, 4 December 2021
Wednesday, 20 May 2020
Wednesday, 26 December 2018
Thursday, 26 July 2018
Why Capacitors bank is connected parallel with a load to improve power factor
Tuesday, 24 October 2017
Monday, 11 September 2017
TRANSFORMER MAINTENANCE GUIDELINES
Sl
No
|
Inspection
Frequency
|
Items
to be inspected
|
Inspection
Notes
|
Action
required if inspection shows unsatisfactory conditions
|
1.1
|
Hourly
|
Ambient Temperature
|
-
|
-
|
1.2
|
Hourly
|
Oil & Winding Temperature
|
Check that temperature rise is
reasonable
|
Shutdown the transformer and
investigate if either is persistently higher than normal
|
1.3
|
Hourly
|
Load (Amperes) and Voltage
|
Check against rated figures
|
Shutdown the transformer and
investigate if either is persistently higher than normal
|
2.1
|
Daily
|
Oil level in transformer
|
Check against transformer oil level
|
If low, top up with dry oil examine
transformer for leaks
|
2.2
|
Daily
|
Oil level in bushing
|
|
|
2.3
|
Daily
|
Relief diaphragm
|
|
Relief diaphragm
|
3.1
|
Quarterly
|
Bushing
|
Examine for cracks and dirt deposits
|
Clean or replace
|
3.2
|
Quarterly
|
Oil in transformer
|
Check for dielectric strength &
water content
|
Take suitable action
|
3.3
|
Quarterly
|
Cooler fan bearings, motors and
operating mechanisms,
|
Lubricate bearings, check gear boxes,
examine contacts
|
Replace burnt or worn contact or other
parts
|
4.1
|
Yearly
|
Oil in transformer
|
Check for acidity and sludge
|
Filter or replace
|
4.2
|
Yearly
|
Oil filled bushing
|
Test oil
|
Filter or replace
|
4.3
|
Yearly
|
Gasket Joints
|
-
|
Tighten the bolts evenly to avoib
uneven pressure
|
4.4
|
Yearly
|
Cable
|
boxes Check for sealing arrangements
for filling holes.
|
Replace gasket, if leaking
|
4.5
|
Yearly
|
Surge Diverter and gaps
|
Examine for cracks and dirt deposits
|
Clean or replace
|
4.6
|
Yearly
|
Relays, alarms & control circuits
|
Examine relays and alarm contacts,
their operation, fuses etc. Test relays
|
Clean the components and replace
contacts & fuses, if required.
|
4.7
|
Yearly
|
Earth resistance
|
|
Take suitable action, if earth
resistance is high
|
GUIDELINES FOR INSTALLING TRANSFORMERS
Sunday, 6 August 2017
What is the reason for choosing frequency 50 or 60 hz not more than this
The choice of high power frequency depends on three factors; two that change over time and one that does not change:
A specific application.
Technology.
Basic laws of physics.
Let's start with # 3. The efficiency of telephone transmission decreases with increasing volume for two main reasons:
The skin effects force the AC currents to the top of the conductor.
Cables emit energy efficiently in high frequency waves. This is good for building antennas, not so good for building a transmission line.
So from a basic physics point of view, the frequency of the appropriate AC power line is zero Hz, that is, DC.
DC also has a peak-to-RMS volume ratio of 1: 1. Since the electrical insulation must withstand its high voltage, DC uses insulation insulation more effectively than AC. (Yes, the square-wave AC also has a voltage ratio of 1: 1 up to RMS, but this includes carrying an infinite number of harmonics - which re-introduces the recently reported disadvantages of high frequencies.)
Now why has DC not become a standard despite basic physics? As a result of considerations # 1 and # 2. The advantages of high power efficiency and (comparatively) low current transmission apply to both AC and DC, but during the Current War between Edison's DC and Westinghouse's AC there was no active DC transformer. So AC won automatically.
But what is the frequency of AC? It's too low, and the lights will flash. (Without DC, of course, but that was not an option without an active transformer.) High frequency transformers are also lighter and smaller than the low frequency AC transformer with the same power, which is why the unusually high frequency of 400 Hz became standard in aviation. Aircraft are also much smaller than the earth's power grid, so transmission losses are not a major problem.
Large electric motors work very well at low AC frequencies, especially the “AC / DC” brush type which has long been used in power grids (railways) due to the need for continuous speed variation. Many power lines live in low frequencies for this reason, e.g., 25 Hz of the Southern Northeast Corridor in the US and 16 2/3 Hz in most of central Europe. DC is even better, and many urban trains (e.g., subways and trams) use it, but also the benefits of high power AC wins when significant distances are involved.
But 50 and 60 Hz were both logical issues for many users for general purposes, which is why they became international standards. Why not one? Because one was as good as the other, and there was no real reason to throw away so many wonderful things that could last so long.
If we could do it again and again from the beginning with modern technology, the strongest case could be made that power systems could and should be completely DC. Thanks to the high power of semiconductor electronics, we now have an effective “DC transformer”. In fact, they “cut” the DC into AC at a very high frequency so that it can be lowered up or down by a transformer (very small and light), and then quickly converted back to DC at a new voltage.
This has already been done for decades on some long-distance transmission lines, especially those that carry very high distances for long distances, below sea level or below.
The same electronics make it possible to drive a simple and powerful AC import engine at any speed you want from a power source at any frequency, including DC. This technology is the basis of modern electric and hybrid vehicles, and it has taken over the railways.
And as the incandescent lamp is quickly replaced by CFL and now LED lights, both of which use electricity, DC is also natural - though it can also easily adapt to any AC supply.
Saturday, 29 July 2017
Monday, 24 July 2017
ELECTRICAL SAFETY
Thursday, 23 March 2017
Voltage or current which is more dangerous
TRANSISTORS
TRANSISTORS A transistor is a semiconductor device that contains three regions separated by two distinct PN junctions. The two junctions are...